The flow determination of
circulating water pump should follow the following principles
(1) When
circulating water by-pass filtration is adopted, the maximum hourly water
consumption plus by-pass filtration shall be the maximum hourly design water
consumption of circulating water pump
(2) When circulating return water
bypass filtration is adopted, the maximum hourly water consumption shall be the
maximum hourly design water consumption of circulating water pump. Determine the
head of circulating water pump. The total head of circulating water pump shall
include the sum of the following values.
(1) The elevation difference
between the allowable lowest water level elevation (or lowest water pressure
elevation) at the water pump suction pipe and the terrain elevation at the most
unfavorable point in the system. (Note: the most unfavorable point refers to the
highest total head of water pump calculated according to this point)
(2)
The required working water pressure at the most unfavorable point.
(3)
Head loss of water pump suction and discharge pipes (including system pipes).
(4) The sum of head loss plus suction height and steam partial pressure
of suction pipe shall be less than the allowable suction height provided by pump
sample.