water ring vacuum pump system working process
The sealed water pump is
to provide enough sealed cooling water for the vacuum pump. Under normal
conditions, the water volume is 200 L / min, and the temperature is 10 ~ 30 ℃.
The circulation process is: sealed water pump → sealed water cooler → vacuum
pump → gas water separator → sealed water pump. The water storage capacity of
the gas water separator and the whole system is 2 m3. The water replenishment
and consumption of the unit in normal operation are less.
In the suction
system of the vacuum unit, the air extractor has two air suction ports. When the
vacuum pump is just started, the air in the vacuum system of the condenser
enters the vacuum pump through the bypass of the air extractor, and then enters
the steam water separator together with the working water. When the negative
pressure at the inlet of the vacuum pump reaches 13.3kpa, the air extractor is
actually started and put into operation, and the bypass valve of the air
extractor is automatically closed. Under normal conditions, when the air
extractor operates for 30min, the negative pressure in the vacuum system of the
condenser can reach the required vacuum value.
The air leakage
measurement system is set in the vacuum pump set, which can measure the air
leakage into the vacuum system at any time safely and conveniently. The method
is to change the status of the movable air converter of the ejector at the inlet
of the driving air from the air flow direction to the direction of the
separator, that is, the air in the separator is used as the driving air source
of the ejector, and the air exhaust valve on the upper part of the tight
air-water separator is closed, so that the true air system of the whole unit
forms a closed system, at this time, all the leakage air flow measuring devices
are opened The inlet valve can easily get the air leakage of the vacuum system.
In this process, the vacuum pump group has been in normal operation, and the
vacuum system of the whole unit is not affected. When the air leakage of air
leakage measuring device is 5kg / h, the corresponding vacuum tightness is
26.66pa, and when the air leakage is 25kg / h, the corresponding vacuum
tightness is 133.3pa. Therefore, as long as the air leakage is less than 25kg /
h in each test, it can be considered that the vacuum system tightness test of
condenser is qualified.
In addition, the ejector heater is also set in
the system. When the temperature of the vacuum pump area is lower than 10 ℃, in
order to ensure the stable operation of the system, the heater must be put into
operation.