Vacuum system of refrigeration equipment
Vacuum pumping is an essential
process before filling refrigerant in the process of production or maintenance
of refrigeration equipment. That is, the vacuum pump is connected with the
refrigeration system pipeline to remove the non condensable gas and water in the
system pipeline.
Hazards of not vacuuming:
Blocking the
pipeline: if the water content of the system exceeds a certain limit, an ice
block will be formed at the capillary outlet, so that the refrigerant can not
circulate normally.
Corrosion: water reacts with refrigerant,
hydrochloric acid and fluorine acid will damage the insulation layer of
compressor.
Copper plating and rusting: the oxygen in the residual air
reacts with hydrochloric acid and copper to produce copper plating, which
corrodes the copper and iron parts in the system pipes and shortens the service
life of system parts.
Decomposition of refrigerant: oxide produced by
corrosion will accelerate the decomposition of refrigerant.
Deterioration and aging of lubricating oil: the oxygen in the residual
air will oxidize the frozen lubricating oil to decompose and deteriorate the
lubricating oil.
Method and process of vacuumizing:
1.
Before operation, check that the vacuum pump is placed horizontally, the sealing
gasket is not damaged, and the pressure gauge of the vacuum gauge is set to
zero.
2. Place the vacuum pump on the indoor ground (safe, stable and
convenient for operation).
3. The fluorine adding tube, vacuum meter and
vacuum pump are combined.
4. Unscrew the nut at the fluorine adding port
from the valve, screw the fluorine adding pipe onto the fluorine adding port,
and confirm whether the thimble is in place.
5. First open the vacuum
meter, then turn on the power switch of the vacuum pump, and start vacuumizing.
The vacuum degree of normal system shall be below - 756mmhg. The vacuumizing
time shall be determined according to the size of refrigeration system and
vacuum pump.
6. After the evacuation operation, quickly remove the
fluorine adding pipe and vacuum gauge, and then fully open the valve again.
After opening the refrigeration system valve, pay attention to whether
the pressure of the vacuum gauge rises. If there is a rise, it means that there
is a leak in the refrigeration system. If there is a leak, find out the cause
and solve it. Then repeat the above vacuum pumping process.
Treatment Of Air Leakage In Vacuum Pump
How To Reduce The Noise Of Water Ring Vacuum Pump
Dry Scroll Vacuum Pump Maintenance